Error Code: F5 - IPM Module Fault ( Intelligent Power Module )

The IPM module is the inverter module which controls the speed of the compressor and the outdoor fan - this is what makes the unit energy efficient. 

To fix the problem with the error code F5, check the following to see if the IPM needs replacing: 

  • Check the connections between the compressor and IPM module are clean and tight
  • Check the IPM module is firmly screwed down to the PCB case
  • An engineer will be needed to check the refrigerant level, low gas can cause the compressor to get hot and send wrong signals back to the compressor 

note: the 9K and 12K systems don't use a seperate IPM module as its built onto the main PCB. The 18K and 24K systems use a seperate IPM module which is mounted next to the main PCB.

If all of the above is good - the connections are clean and tight, the refrigerant is at the right level - then the IPM module needs replacing. 

To purchase a new IPM module you can contact us via email at info@airconditioningcentre.com or call us at 0370 3344 556.

  • 28 Users Found This Useful
Was this answer helpful?

Related Articles

Error Code: F1 - Communication Fault

The error code ' F1' means the indoor unit PCB and outdoor unit PCB cannot communicate with each...

Error Code: F2/F3 - Internal Temperature Sensor Fault

Both error codes signify that there's a problem with the internal sensor. The difference between...

Error Code: F4 - Internal Fan Fault

The error code 'F4' is indicating either a fault with the indoor fan motor or indoor PCB. To...

Error Code: F6/F7/F9 - External Temperature Sensor Fault

All 3 error codes means there is something wrong with the sensors - the difference between the...

Error Code: FC - Compressor Drive Fault

This error is signifying a fault between the compressor and external PCB.  To fix the error code...